Flowserve NRS 1-50 For TWO Electrodes User Manual

Browse online or download User Manual for Hardware Flowserve NRS 1-50 For TWO Electrodes. Flowserve NRS 1-50 For TWO Electrodes User Manual

  • Download
  • Add to my manuals
  • Print

Summary of Contents

Page 1 - NRS 1-50

1Installation Instructions 818953-01Level Switch NRS 1-50GESTRA Steam SystemsGESTRA ENEnglishNRS 1-50 For TWO Electrodes

Page 2 - Contents

10Name plate / markingFig. 5Type designationMains voltage/ ProtectionSerial numberManufacturerWiring diagramSafety noteDisposal noteTechnical Data

Page 3 - Contents – continued –

11Fig. 6Dimensions and Functional ElementsNRS 1-501234 5671 Upper terminal strip2 Lower terminal strip3 Fixing screws (cross recess head screws M3)

Page 4 - Application

12Safety noteWater level limiters are safety devices and must only be installed, wired and commissioned by qualified and competent staff.Retrofitting a

Page 5 - Directives and Standards

13Electrical ConnectionConnection of level electrodeTo connect the level electrode(s) use screened multi-core control cable with a min. conductor size

Page 6

14Electrical Connection – continued –Toolsn Screwdriver for slotted screws, size 3.5 x 100 mm, completely insulated according to VDE 0680-1.Dangern

Page 7

1527161 2 3 4 5 6 7 817 18 19 20 21 22 23 24925102611 12281329143015NRG 1...-50NRG 16-36M 0,5ANRG 1...-501211242333Electrical Connection – continued

Page 8 - Technical Data

16ddeef fd defefddgeffFig. 8 Fig. 9Fig. 10 Fig. 11Fig. 12 Fig. 13Electrical Connection – continued – Schematic representations of arrangementseed L

Page 9

17Electrical Connection – continued – Explanatory notes to schematic respresentationsSteam boiler plants according to TRD 604, EN 12952-07 / EN 1295

Page 10 - Technical Data – continued –

18Commissioning ProcedureChanging configurationDangerThe terminal strips of the NRS 1-50 are live during operation.This presents the danger of electric

Page 11

19Commissioning – continued –Checking switchpoint and functionStartActivity Indication FunctionApply mains voltage. All LEDs are illuminated.System

Page 12 - Important Notes

2ContentsUsage for the intended purpose ...

Page 13 - Installation

20OperationActivity Indication FunctionLevel electrode(s) submerged.Green LEDs for level electrode 1 / 2 illuminated.Output contacts are closed. Sig

Page 14 - – continued –

21Fault Indication and Troubleshooting – continued –Diagnosis Display 1 and activity Display 2 Fault Remedy LED alarm 1 and diagnosis LED 1 illumina

Page 15

22Measure the electrode voltage in order to check whether the level electrode is immersed or if there is a malfunction. Please observe Fig. 15. ≈ 0.7

Page 16 - Fig. 12 Fig. 13

23Emergency operationEmergency operation for water level limiterIf the level switch NRS 1-50 works with two level electrodes NRG 1...-50 (water level

Page 17

24Action against high frequency interferenceShould sporadic failures occur in installations susceptible to faults (e. g. malfunctions due to out-of-ph

Page 21 - – continued –

28818953-01/12-2009cm (808805-03) · GESTRA AG · Bremen · Printed in GermanyGESTRA Agencies all over the world:www.gestra.deGESTRA AGP. O. Box 10 54 60

Page 22 - Malfunction (immersed/alarm)

3Contents – continued –Changing configuration ...

Page 23 - Emergency operation

4ApplicationUsage for the intended purposeThe level switch NRS 1-50 is used in conjunction with level electrodes NRG 1...-.. to limit the water level

Page 24 - Further Notes

5Directives and StandardsPressure Equipment Directive (PED) 97/23/ECWater level limiters are safety accessories as defined in the Pressure Equipment Di

Page 25 - For your notes

6Functional Safety acc. to IEC 61508Safety characteristics of the subsystem NRG 1...-50 / NRS 1-50The level switch NRS 1-50 is certified acc. to IEC 61

Page 26

7Functional Safety acc. to IEC 61508 – continued –Determination of the Safety Integrity Level (SIL) for safety-related systemsLevel electrode, level

Page 27

8NRS 1-50Supply:Mains voltage 24 VDC +/– 20 %, 0.3 A or 100-240 VAC + 10/– 15 %, 47-63 Hz, 0.2 AExternal fuse 0.5 A (semi-delay)Power consumption 7 VA

Page 28 - GESTRA AG

9NRS 1-50 – continued –Further conditions: Ambient temperature when system is switched on: 0 ° ... 55 °C during operation: –10 ... 55 °CTransport te