Page view 3
LME0005-1 (AUTO-43) 07/03
©
2003, Flowserve Corporation, Printed in USA
3-Position Control/Dribble Control
SR Limit Switch Method
Flowserve Corporation 1350 N. Mountain Springs Parkway 1978 Foreman Dr.
Flow Control Division Springville, Utah 84663-3004 Cookeville, TN 38501
www.flowserve.com Phone: 801 489 8611 Phone: 931 432 4021
Automax Valve Automation Systems
Installation, Operation and Maintenance Instructions
Page 4 of 4
CENTURA Series Actuator - CE Extras
Size Motor Switches Options Conduit (can add more than one)
250 in-lbs -2 12 VDC (without brake) -B One extra -1 DC Motor Controller -DA Right Hand -Blank Epoxy Coating -E
400 in-lbs -4 24 VDC (without brake) -C Two extra -2 4-20mA Transmitter -TX Both Left & Right -X Heater & Stat -H
700 in-lbs -7 Three extra -3 0-135 Ohm Potentiometer -P1 Manual Handwheel -Z
1,000 in-lbs -1 Four extra -4 0-1000 Ohm Potentiometer-P2
1,500 in-lbs -5 0-5000 Ohm Potentiometer-P3
0-10K Ohm Potentiometer -P4
0-1000, 0-10K Dual Pot -P6
Troubleshooting Guide
1. No LED indicators lit:
A. DC Power Supply not on
B. On-board fuse blown, check for proper
power polarity and voltage level at
+++/POWER and GND (TB1 pins 7 and
8), replace fuse.
C. LED switch set to OFF
2. Actuator is not responding to remote inputs:
A. Ensure on-board local control switches
LOCAL/REMOTE are set to REMOTE.
B. Check polarity of signaling terminal
wiring, and proper voltage measurements,
see Page 3, Input Configurations.
C. Check LED F (fault) latch set, adjust
I SENSE adjustment as required,
following instructions on Page 2.
D. Check that jumpers J3 & J4 are both on
left two posts or both on right two posts
as desired. See diagram on Page 3 for directions.
DC Motor Actuator Specifications
DC Motor System 12V 24V
Supply Voltage (maximum) 14V 28V Volts
Remote Signal (18AWG) 5000 5000 ft.
Cycle Time*, (min/max adj)
CE2B, CE2C 6-14 6-14 sec.
CE4B, CE4C 8-20 8-20 sec.
CE7B, CE7C 15-31 15-31 sec.
CE1B, CE1C 20-42 20-40 sec.
CE5B, CE5C 32-60 30-60 sec.
Supply Currents (typ.)
Controller Board 10** 15** mA
DC Motor (full load) 1.60 0.9 A
I Sense Adj. (max) 2.0 2.0 A
Operating Temperature -40 to 160 Deg. F
(-40 to 70 Deg. C)
* - Times are approximate under no load conditions and
may vary slightly under actual operating conditions.
** - Board options set at minimum current draw.
How to Order
(Select from each column)
Weight CE2, CE4, CE7, CE1 = approx. 18 lbs., CE5 = approx. 20 lbs.
Ordering Example: Automax CENTURA Series Electric Rotary Actuator capable of 400 in-lbs. torque, to operate on 12 VDC with DC Motor
Controller would read: CE4BDA
*Flowserve can supply special mounting on the bottom of the CENTURA Series actuators to direct couple to many common valve lines.
**No mechanical solenoid brake as supplied on AC Actuators.
**
Page view 3