NRS 1-51
Installation Instructions 818955-01
Level Switch
NRS 1-51
GESTRA Steam Systems
GESTRA
EN
English
Page view 0
1 2 3 4 5 6 ... 23 24

Summary of Contents

Page 1 - NRS 1-51

1NRS 1-51Installation Instructions 818955-01 Level SwitchNRS 1-51GESTRA Steam SystemsGESTRA ENEnglish

Page 2 - Contents

10Name plate / markingFig. 5Type designationMains voltage/ ProtectionManufacturerWiring diagramSafety noteDisposal noteTechnical Data – continued –

Page 3

11Fig. 6Dimensions and Functional ElementsNRS 1-51123671 Upper terminal strip2 Lower terminal strip3 Fixing screws (cross recess head screws M3)6

Page 4 - Application

12Safety noteHigh water level alarms are safety devices and must only be installed, wired and commissioned by qualified and competent staff.Retrofitting

Page 5 - Directives and Standards

13Electrical ConnectionConnection of level electrodeTo connect the level electrode use screened multi-core control cable with a min. conductor size 0

Page 6

14Electrical Connection – continued – Toolsn Screwdriver for slotted screws, size 3.5 x 100 mm, completely insulated according to

Page 7

1527161 2 3 4 5 6 7 817 18 19 20 21 22 23 24925102611 12281329143015NRG 1...-51123+ -M 0,5AElectrical Connection – continued – Fig

Page 8 - Technical Data

16ddeeffFig. 8Fig. 9Electrical Connection – continued – Schematic representations of arrangementsKeySteam boiler plants according

Page 9 -

17Commissioning ProcedureChecking switchpoint and functionStartActivity Indication FunctionApply mains voltage. All LEDs are illuminated.System is bei

Page 10 - NRS 1 - 51

18OperationActivity Indication FunctionLevel electrode exposedGreen LED for level electrode 1 is illuminatedOutput contacts are closed. Signal outpu

Page 11

19Diagnosis Display 1 and activity Display 2 Fault Remedy LED alarm 1 and diagnosis LED 1 illuminated. Press and hold down key 1.Diagnosis LED 1 flash

Page 12 - Important Notes

2ContentsUsage for the intended purpose ...

Page 13 - Installation

20Action against high frequency interferenceShould sporadic failures occur in installations susceptible to faults (e. g. malfunctions due to out-of-ph

Page 14

21For your Notes

Page 15

22For your Notes

Page 16

23For your Notes

Page 17 - Commissioning Procedure

24818955-01/12-2009cm (808806-01) · GESTRA AG · Bremen · Printed in GermanyAgencies all over the world:www.gestra.deGESTRA AGP. O. Box10 54 60, D-2805

Page 18 - Troubleshooting

3Contents – continued – Checking switchpoint and function ...

Page 19

4ApplicationUsage for the intended purposeThe level switch NRS 1-51 is designed for different electrical conductivities of the boiler water and for co

Page 20 - Further Notes

5Directives and StandardsPressure Equipment Directive (PED) 97/23/ECThe level switch NRS 1-51 in conjunction with level electrode NRG 1...-51 is EC ty

Page 21 - For your Notes

6Functional Safety acc. to IEC 61508Safety characteristics of the subsystem NRG 1...-51 / NRS 1-51The level switch NRS 1-51 is certified acc. to IEC 61

Page 22

7Functional Safety acc. to IEC 61508 – continued – Determination of the Safety Integrity Level (SIL) for safety-related systemsLev

Page 23

8NRS 1-51Supply:Mains voltage 24 VDC +/– 20 %, 0.3 A or 100 – 240 VAC +10/–15 %, 47 – 63 Hz, 0.2 AExternal fuse 0.5 A (semi-delay) Power consumption 7

Page 24 - GESTRA AG

9NRS 1-51 – continued – Further conditions: Water quality (max. admissible electrical conductivity of the boiler water) steam boil