Important notes
The installation of two low-level limiters in one standpipe is not allowed according to
TRD!
For the approval of the boiler standpipe the relevant regulations must be observed.
For typical installation examples refer to page 14.
When mounting the electrode laterally make sure that the inclination angle does not
exceed 45° and that the length of the electrode rod is limited to 1000 mm.
Fig. 11
If the electrode is installed outdoor, it must be provided with a weather-proof cover
supplied by GESTRA.
Tools
Open-end spanner A. F. 13
Open-end spanner A. F. 36
Scriber
Hacksaw
Flat file, cut 2
Installation – continued –