Flowserve ACE Series Centura User Manual Page 7

  • Download
  • Add to my manuals
  • Print
  • Page
    / 8
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 6
©
2004, Flowserve Corporation, Printed in U.S.A.
3-Position Control/Dribble Control
SR Limit Switch Method
Accord Controls
Installation, Operation and Maintenance Instructions
Flowserve Corporation 1350 N. Mountain Springs Parkway Phone: 801 489-2234
Flow Control Division Springville, Utah 84663-3004 Facsimile: 801 489-2228
www.flowserve.com
FCD ACAIM0075-00 (AC-75) 08/04 Page 7 of 8
Typical Actuator Specifications
Action Reversible
Range of Adjustability 0° -270°
Supply Voltages AC: 115 VAC
+/-10% 230 VAC
50/60 Hz 24 VAC
DC: 12 VDC
24 VDC
Temperature Rating -40°F (-40°C) to 160°F (70°C)
Enclosure Ratings Nema 4, 4X, 7, 9 Watertight and Explosion-proof
Class I Groups C&D, Div. 1&2
Class II Groups E, F&G, Div. 1&2
Motor Types AC: Permanent Split Capacitor, Class B Insulation
DC: Brush
AC Motor Thermal Protection Automatically resetting
Travel and Aux. Switches SPDT, Form C
15 amp 125 VAC 1/2 HP,
10 amp 250 VAC, 1/2 amp 125 VDC
Conduit Connections 3/4-14 NPT
Manual Override 300 In-lbs max input
Corrosion Protection Chromate conversion undercoat with
polyester electrostatic powder top coat
Terminal Strip Hookup 300V, 30 amp, 12-26 AWG
Lubrication Permanently lubricated
Gear Train Heat treated alloy steel able to
withstand stall torque
Note: The above ratings may change depending on model configurations and options provided.
Products may differ as the result of the Company policy of continuous product improvement.
Notes:
1. Duty cycle is the limit of “on” time as percentage of total cycle time. For example, the CE2 with standard
motor runs 3 seconds to open or close the valve. The motor must remain off for 9 seconds prior to
starting the close cycle. DC motors may be operated continuously.
2. Do not lock up DC motors.
3. CE5 duty cycles for AC motors are 20% for standard duty and 70% for extended duty.
4. For 180 degree applications, simply multiply the above cycle times by 2.
Run Locked Cycle Times in Seconds per 90 Degrees
Motor Motor Duty Current Rotor Actuator Model
Option Voltage Cycle (1, 3) (Amps) (Amps) CE2 CE4 CE7 CE1 CE5
Std. 115 AC 25 1.1 1.3 3 5 6 11 18
A 115 AC Extended: 75 0.5 0.6 6 10 17 24 36
B 12 DC 100 1.6 3.0 (2) 6 9 16 21 32
C 24 DC 100 0.9 2.0 (2) 6 8 15 20 30
D 230 AC 25 0.7 0.8 3 5 6 11 18
F 230 AC Extended: 75 0.3 0.4 6 10 17 24 36
J 24 AC 100 0.5 0.8 3 5 6 11 18
Actuator Model
CE2 CE4 CE7 CE1 CE5
Torque (In-Lbs) 250 400 700 1000 1500
Torque (N-M) 28 45 79 113 169
Weight (Lbs) 18 18 18 18 20
Weight (Kg) 8 8 8 8 9
Page view 6
1 2 3 4 5 6 7 8

Comments to this Manuals